Fire door inspection checklist

A fire door inspection form for blocks of flats. Check each door for damage, glazing, hinges, seals, gaps and whether it closes fully, then record the round totals, the 12 month flat entrance door record, remedial work and the information given to residents. Film each door with Walk Cam and the AI inspector suggests pass, fail or cannot assess for you to confirm. Every question is listed below, and you can fill the live form in on this page.

Ready to use from the form library, and every question is yours to edit. Trial from £1, cancel any time.

Try it on your phone

Try it on this phone

Fill in the fire door inspection on your phone now

See how the fire door inspection looks on your phone

Scan the code with your phone camera. It opens the real form, no sign-up needed.

Open the live example and fill it in, just as your team would on site. No sign-up needed.

See it on this phone

Every question is editable. Add this form to your account, then change the wording, add or remove questions and options, and make it fit your own jobs.

Or start your trial with this form ready →

One email, and we won't add you to a mailing list.

What should a fire door inspection checklist include?

A fire door inspection checklist should record each door's location and type, any damage or alteration, glazing, hinges, intumescent strips and smoke seals, the gaps around the door and whether it closes fully into the frame. GOV.UK guidance says the gap between door and frame should never be more than 4 mm, except at the bottom. Failed doors need a remedial action and date.

Last updated . Facts checked by the SiteSurvey team on 24 October 2026 against regulation 10 of the Fire Safety (England) Regulations 2022, GOV.UK fire door guidance and the regulation 10 fact sheet.

Built for checking fire doors floor by floor

Record each floor and each door on a phone as you go. Measure the leaf from a photo, gauge the gaps, photograph each defect, and let the form count the doors checked, failed and to fix today, floor by floor and for the round.

Door leaf height 1990 mm and width 870 mm on a phone, each with a measuring photo thumbnail, under guidance to hold an A4 sheet flat on the door and use a gap gauge for the gaps

Leaf size from a photo

Hold an A4 sheet flat on the door, tap its long edge, then the top and bottom of the leaf. Rounded to 10 mm, it identifies the door set or briefs a replacement survey; it is not for making a leaf. It works on web forms in any phone browser today, and the app version is on its way.

How measuring from a photo works →

Gaps with a gauge, on camera

A photo cannot measure a 3 mm gap, so the form asks for the gaps from a gauge and flags any over 4 mm, and the gap under the door against its own limit. Film the edges with the gauge in shot and the AI inspector reads it and suggests a verdict for you to confirm.

How the AI inspector works →
Round totals worked out on a phone: doors checked 4, doors that failed 2, failed doors to fix today 1, with a red note to make it safe before leaving site

Fails counted for you

Each floor counts its doors checked, failed and to fix today, and the round adds them up with the share that passed and the doors still to check. A door to fix today brings up a reminder before you leave.

How calculated fields work →

A completed fire door inspection

A quarterly check of a fictional block of flats above 11 m: five doors over three floors, a stair door that will not latch, a corridor door with a 12 mm gap underneath and a damaged seal, and a flat with no access after four dated attempts. Open it as a filled-in form, or switch to a blank copy and try it yourself.

A white fire door with an A4 sheet taped to it, measured from the photo at about 1990 mm from the head of the leaf to the threshold
FD-03-02 · leaf about 1990 x 870 mm · gaps by gauge
An overhead door closer arm hanging loose from its bracket above a red fire door
FD-G-01 · closer loose, door not latching · fix today
A torn intumescent strip in the hinge edge of a fire door frame
FD-03-02 · hinge side seal damaged

New: AI inspector · Coming in the next app update

Film each door and let the AI inspector check it with you

This form's Walk Cam field ships with an inspector brief: four points and 18 checks drawn from the regulation 10 quarterly checks. Film a point on the SiteSurvey app and six to ten seconds later the AI suggests pass, fail or cannot assess, with each defect boxed on a still from your clip. You confirm every point. Only confirmed verdicts and accepted photos reach the door record and the report.

  1. Film the point

    Hold record and film what the point card asks for: the whole door, the gaps with a gauge in them, the seals, the door closing. Let go and move on while it checks.

  2. Read the suggested verdict

    Pass, fail or cannot assess, with a short summary and each finding boxed in red on a still from your clip. If it could not see enough it says what to film instead.

  3. Confirm, change or dismiss

    Accept the verdict or change it to the one you would give. Dismiss a finding you disagree with and add a note. The report prints your confirmed verdict and names you, not the model.

What it checks on the fire door inspection form: 4 points, 18 checks

Point 1 · Door and signage

Film the whole door closed, then both faces, the door reference and the signage.

  • Door leaf and frame free of damage, splits, holes, warping or unauthorised alteration
  • Door sits in the frame with no visible daylight around the leaf
  • Glazing, where present, intact with beading and seals undamaged
  • Fire door keep shut or keep locked sign present and legible on the required face
  • Certification label or plug visible, if one is fitted

Point 2 · Gaps

Show the gap under the door and at the head and both edges, with a gauge or ruler in the gap.

  • A gauge or ruler is visible in the gap so the measurement can be read
  • Gap at the head and both sides between 2 mm and 4 mm
  • Gap under the door no more than 10 mm, unless the door's own documents allow more
  • No gap between the frame and the surrounding wall

Point 3 · Seals

Show the intumescent strips and cold smoke seals all the way round the leaf or frame.

  • Intumescent strip present on every required edge and continuous
  • Cold smoke seal present, continuous and not flattened or torn
  • Strips and seals not painted over or damaged
  • Three hinges fitted, secure, with no missing screws or visible wear

Point 4 · Closer

Open the door fully and let it go, then open it about 75 mm and let it go, so it is clear whether it closes and latches each time.

  • Self-closing device fitted and undamaged, with no leaking oil
  • Door closes fully into the frame from fully open
  • Door closes and latches from about 75 mm open
  • No wedges, hooks, ties or unapproved hold-open devices
  • Latch engages and handles are secure

The AI never estimates a gap by eye. With no gauge in shot the gap checks come back as cannot assess and it asks for the gauge shot. A wedged, propped or tied door is a fail. Whether a door is the right type for its location stays with the fire risk assessment, as it does on the rest of this form.

It is coming in the next SiteSurvey app update, in early access. Switched on per company during early access: ask support to turn it on for your account. Clips are assessed by Google Gemini and are not used to train Google's models. Included in the subscription, with no per-clip charge.

Screen recording of the AI inspector on a fire door walk: the Seals point is filmed, the findings sheet suggests Fail with the torn strip boxed in red on a still, Accept Fail is tapped, and the form shows the confirmed verdicts with the boxed stills
Recorded on the phone on this form: the Seals point, a torn strip, suggested Fail, confirmed by the inspector.

Try the fire door inspection form live

Answer a few questions and watch it adapt. Your answers are not saved, and any photos you add are deleted within the hour.

Live form: Fire Door InspectionOpen full screen ↗
Fill it in right here

This is the real form as your team would use it: questions appear as you answer, scores work themselves out and you can add photos and signatures. No sign-up needed. Or open a completed example to see every answer, photo and score filled in.

Want to see one filled in? See a completed fire door inspection report (PDF), made by SiteSurvey from a fictional site visit.

Walk Cam route · four guided clips

Record the fire door inspection on video

Show door identity, leaf and frame, accessible seals and hardware, then document what needs a proper operational check.

Identify the building and door. Film the leaf, frame, accessible seals and hardware without alteration. Refer concerns to the Responsible Person and complete any required closer test separately.

See the footage in a report

A fictional six-page example with the four points, twelve stills from the clips, observations, follow-up actions and the limits of a visual record.

View the visual evidence (PDF) ↗ · Download the full sample report

Visual evidence page from the fire door condition visual inspection sample report, with footage stills and observations

Video shows visible condition only. It cannot prove fire resistance, certification, measured gaps, seal suitability or closer operation. The Responsible Person must complete applicable checks and records separately. Example footage was generated in Google Flow and the observations are scripted; no real site is shown. Walk Cam works inside any form in the app. How Walk Cam works · All visual inspections

For teams

Using the fire door inspection template for client work?

Paper or a spreadsheet works for the odd job. When your team does this every week, SiteSurvey keeps every visit in one place and turns each one into a report you can send.

  • Everyone fills in the same form on their phone, with photos attached to the answer they belong to.
  • Each visit becomes a branded PDF report for the client, with no retyping.
  • Every site, visit and report is kept together in one account, not scattered across email and shared drives.

Fill it in on a phone or tablet

Your team completes the fire door inspection on site in the SiteSurvey app on iPhone, iPad and Android phones and tablets. The project name and address fill in for them, it works without signal, and it syncs when the device is back online with photos kept against the question they answer.

Customers and subcontractors do not need the app: send them a link and they can fill it in from any browser.

The Fire Door Inspection form in the SiteSurvey app on a tablet
The Fire Door Inspection form in the SiteSurvey app on a phone

Every question in the fire door inspection template

Door by door checks (gaps, seals, closers, signage, glazing), 12 month flat entrance door record and remedial work list. 7 sections and 89 questions. Follow-up questions and guidance appear only when an answer calls for them, so the person on site never sees the ones that do not apply.

Make it your own: every question is editable

This is a starting point, not a fixed form. Once it is in your SiteSurvey account you can reword any question, add or remove questions, sections and answer options, and add your own logo, so it fits the way your team works and the jobs you do.

Details you only enter once

Add this form to a project in SiteSurvey and it fills in what the project already knows, so nobody on site retypes it and every form on the job uses the same names. Anything filled in can still be changed.

  • Project: the project name
  • Client or responsible person: the project's customer
  • Site or block: the site, when the form is opened for a space or a product

Building and check details

Which building, which doors and who is checking them.

  • ProjectShort answer

    Filled in from the project in SiteSurvey.

    Fills in from the project name
  • Client or responsible personShort answer
    Fills in from the project's customer
  • Site or blockShort answer
    Fills in from the site, when the form is opened for a space or a product
  • Report referenceShort answer
  • Building name and address*Short answer
  • Date of the check*Date
  • Which doors are being checked?*Choose one
    • Doors in communal areas
    • Flat entrance doors
    • Both
  • Is the top storey of the building more than 11 metres above ground?Yes or No
  • CheckSources. The Fire Safety (England) Regulations 2022, regulation 10: in a building in England containing two or more sets of domestic premises with a top storey more than 11 metres above ground level, the responsible person must check fire doors in communal areas at least every 3 months, use best endeavours to check flat entrance doors at least every 12 months, keep a record of the checks and the steps taken to gain access, and give residents fire door information. The Regulatory Reform (Fire Safety) Order 2005, article 17, requires fire doors in all premises it covers to be maintained.
  • GuidanceDoors in communal areas. In a block of flats above 11 metres in height, in England, these must be checked at least every 3 months.
    Shown only when the answers above make it relevant
  • GuidanceFlat entrance doors. In a block of flats above 11 metres in height, in England, the responsible person must use best endeavours to check these at least every 12 months, and keep a record of the steps taken.
    Shown only when the answers above make it relevant
  • CheckThe Fire Safety (England) Regulations 2022, regulation 10, set no check frequency for this building. The Regulatory Reform (Fire Safety) Order 2005 still requires a suitable system of maintenance, so follow the fire risk assessment.
    Shown when “Is the top storey of the building more than 11 metres above ground?” is No
  • Date of the previous check of these doorsDate
  • Is there a fire risk assessment that covers the doors?Yes or No
  • CheckThese checks are simple and visual. Whether each door is the right type for its location is a matter for the fire risk assessment. Tell the responsible person that you could not find one.
    Shown when “Is there a fire risk assessment that covers the doors?” is No
  • Can you reach every door on the schedule today?Yes or No
  • Which doors can you not reach, and why?Notes
    Shown when “Can you reach every door on the schedule today?” is No
  • Walk Cam: Fire door inspectionWalk Cam video with voice-to-text

    Optional. Film a guided walk-through on the SiteSurvey app. The AI inspector reviews each point and suggests a verdict for you to confirm.

Door records

One entry for each door. The checks are visual and need no tools.

  • GuidanceWhat a good photo shows. The gap with a gauge or tape in shot, the strip or seal along the edge, and the closer with its fixings.
  • The gap under a fire door above a carpeted floor
    The gap under a fire door above a carpeted floor
    A torn intumescent strip on the edge of a fire door
    A torn intumescent strip on the edge of a fire door
    An overhead closer fixed above a red fire door
    An overhead closer fixed above a red fire door
  • Floors and areas
    Repeat for each entry. Each one asks:
    • Floor or area*Short answer

      For example Ground floor, Level 3 landing or Flats 7 to 12

    • Doors on this floor
      Repeat for each door. Each one asks:
      • Door referenceShort answer
      • Where on this floorShort answer

        For example Flat 12 entrance or stair core door

      • Type of doorChoose one
        • Flat entrance door
        • Stairway or lobby door
        • Corridor door
        • Plant room, service cupboard or riser door
      • Fire resistance rating shown on the door, if anyShort answer
      • Was access to the flat given, so both sides of the door could be checked?Yes or No
        Shown when “Type of door” is “Flat entrance door”
      • Steps taken to gain accessTick all that apply
        • Letter or email to the resident
        • Visit, with a card left
        • Phone call or text
        • A choice of times offered
        • Other (describe)
        Shown when “Type of door” is “Flat entrance door” and “Was access to the flat given, so both sides of the door could be checked?” is No
      • Dates of each attempt, and the outcomeNotes
        Shown when “Type of door” is “Flat entrance door” and “Was access to the flat given, so both sides of the door could be checked?” is No
      • CheckAccess not granted. Regulation 10 requires a record of the steps taken to check flat entrance doors, including the steps taken to try to gain access.
        Shown when “Type of door” is “Flat entrance door” and “Was access to the flat given, so both sides of the door could be checked?” is No
      • Has the door been replaced with one that may not be fire resisting?Yes or No
        Shown when “Type of door” is “Flat entrance door” and “Was access to the flat given, so both sides of the door could be checked?” is Yes
      • CheckWhere there is any doubt, the guidance says the resident will need to confirm that the new door is fire resisting and was installed by a competent person.
        Shown when “Type of door” is “Flat entrance door” and “Has the door been replaced with one that may not be fire resisting?” is Yes
      • LetterboxChoose one
        • Closes firmly
        • Jammed open or damaged
        • No letterbox
        Shown when “Type of door” is “Flat entrance door” and “Was access to the flat given, so both sides of the door could be checked?” is Yes
      • Any damage or alteration to the door, frame or surrounding wall?Yes or No
        Shown only when the answers above make it relevant
      • What is damaged or altered, and where?Notes
        Shown when “Any damage or alteration to the door, frame or surrounding wall?” is Yes
      • Glass and glazing in the door or side panelsChoose one
        • No glazing
        • Sound
        • Cracked, loose or damaged
        Shown only when the answers above make it relevant
      • Hinges and other ironmongery free of obvious defects?Yes or No
        Shown only when the answers above make it relevant
      • What is wrong? For example missing or loose screwsShort answer
        Shown when “Hinges and other ironmongery free of obvious defects?” is No
      • Air transfer grillesChoose one
        • None fitted
        • Undamaged
        • Damaged
        Shown when “Type of door” is “Plant room, service cupboard or riser door”
      • Intumescent strips and smoke sealsChoose one
        • Undamaged and in contact
        • Damaged or missing in places
        • Painted over
        • None fitted
        Shown only when the answers above make it relevant
      • Where is the damage?Tick all that apply
        • Hinge side
        • Latch side
        • Top
        • Bottom
        Shown only when the answers above make it relevant
      • GuidanceIf strips and seals were not originally fitted, this may be acceptable. It depends on the findings of the fire risk assessment, so refer it to the assessor.
        Shown when “Intumescent strips and smoke seals” is “None fitted”
      • Door leaf height (mm)Number

        From a photo, hold an A4 sheet flat on the door as the reference. The result is rounded to 10 mm: enough to identify the door set or brief a replacement survey, not to make a leaf. Measure the gaps with a gap gauge.

        Shown only when the answers above make it relevant
      • Door leaf width (mm)Number
        Shown only when the answers above make it relevant
      • Gap at the top (mm)Number
        Shown only when the answers above make it relevant
      • Gap, hinge side (mm)Number
        Shown only when the answers above make it relevant
      • Gap, latch side (mm)Number
        Shown only when the answers above make it relevant
      • CheckGap over 4 mm. GOV.UK guidance gives the industry standard: the gap between the door and the frame should never be more than 4 mm, except at the bottom of the door.
        Shown only when the answers above make it relevant
      • Gap under the door (mm)Number
        Shown only when the answers above make it relevant
      • Limit for this door, from its own documents (mm)Number
        Shown only when the answers above make it relevant
      • GuidanceGOV.UK guidance gives no figure for the gap under a door. It should be as small as practicable, without the door catching on the floor. Take the limit from the door's own documents or the fire risk assessment.
        Shown only when the answers above make it relevant
      • Over the limit by (mm)Worked out by the form
        Shown only when the answers above make it relevant
      • CheckThe gap under this door is larger than the limit you entered for it. Record the remedial action below.
        Shown only when the answers above make it relevant
      • How is the door kept closed?Choose one
        • Self-closing device
        • Held open on a magnetic device
        • Kept locked shut
        Shown only when the answers above make it relevant
      • GuidanceUse the test button, where there is one, to release the door. Do not pull the door from its magnet.
        Shown when “How is the door kept closed?” is “Held open on a magnetic device”
      • Opened fully and let go: did it close fully into the frame?Yes or No
        Shown only when the answers above make it relevant
      • Opened to about 15 degrees and let go: did it close fully into the frame?Yes or No
        Shown only when the answers above make it relevant
      • WarningThe door does not close fully. A fire door that does not close fully into its frame will not adequately hold back fire and smoke. Regulation 10 requires the check to make sure the self-closing device is working.
        Shown only when the answers above make it relevant
      • What stops it closing?Notes
        Shown only when the answers above make it relevant
      • ResultChoose one
        • Pass
        • Fail
        • Not checked
      • Which looks most like the main defect?Choose one
        • Large gap under the door
        • Damaged strip or seal
        • Closer loose or not closing
        Shown when “Result” is “Fail”
      • Photos of the defectPhotos
        Shown when “Result” is “Fail”
      • Remedial actionNotes
        Shown when “Result” is “Fail”
      • PriorityChoose one
        • Today
        • This week
        • This month
        Shown when “Result” is “Fail”
      • Why was the door not checked?Short answer
        Shown when “Result” is “Not checked”
      • Photos of the doorPhotos
    • This floor: doors checkedWorked out by the form
    • This floor: doors failedWorked out by the form
    • This floor: to fix todayWorked out by the form

Round totals

Count the doors so the record shows what was and was not checked.

  • Doors on the schedule for this roundNumber
  • Doors checkedWorked out by the form
  • Doors that failedWorked out by the form
  • Failed doors to fix todayWorked out by the form
  • WarningAt least one door failed with priority Today. Make it safe or tell the responsible person before you leave site.
    Shown only when the answers above make it relevant
  • Doors passedWorked out by the form
    Shown only when the answers above make it relevant
  • Share of checked doors that passed (%)Worked out by the form
    Shown only when the answers above make it relevant
  • Doors not checkedWorked out by the form
    Shown only when the answers above make it relevant
  • CheckSome doors on the schedule were not checked. List them and say when they will be checked.
    Shown only when the answers above make it relevant
  • Doors not checked, and the date planned for themNotes
    Shown only when the answers above make it relevant
  • Date the next check of the communal doors is dueDate
    Shown only when the answers above make it relevant

Flat entrance doors: 12 month record

The running total for the block over the last 12 months.

  • Flats in the blockNumber
  • Flat entrance doors checked in the last 12 monthsNumber
  • Share checked (%)Worked out by the form
    Shown only when the answers above make it relevant
  • Flats still to checkWorked out by the form
    Shown only when the answers above make it relevant
  • Were there flats where access was not granted?Yes or No
  • Which flats, and what steps were taken to gain access?Notes
    Shown when “Were there flats where access was not granted?” is Yes
  • What will be tried next?Notes
    Shown when “Were there flats where access was not granted?” is Yes

Remedial work

What needs repair, who will do it and by when.

  • Did any door fail?Yes or No
  • WarningGOV.UK guidance says that where a check finds a fire door needs repair or replacement, the work must be done by a competent contractor as soon as reasonably practicable.
    Shown when “Did any door fail?” is Yes
  • Remedial actions by door
    Repeat for each action. Each one asks:
    Shown when “Did any door fail?” is Yes
    • Door referenceShort answer
    • Action*Notes
    • PriorityChoose one
      • Urgent
      • High
      • Medium
      • Low
    • ContractorShort answer
    • DueDate
    • StatusChoose one
      • Open
      • In progress
      • Completed
  • Who will do the work?Short answer
    Shown when “Did any door fail?” is Yes
  • Target dateDate
    Shown when “Did any door fail?” is Yes
  • Anything done on the dayNotes
    Shown when “Did any door fail?” is Yes
  • Will each door be checked again after the repair?Yes or No
    Shown when “Did any door fail?” is Yes
  • Does anything need to go to the fire risk assessor?Yes or No
  • What, and why?Notes
    Shown when “Does anything need to go to the fire risk assessor?” is Yes

Information for residents

Residents must be told how to look after fire doors.

  • GuidanceRegulation 10 requires residents to be told that fire doors should be kept shut when not in use, that self-closing devices should not be tampered with, and that faults or damage should be reported immediately.
  • Has this information been given to all residents in the current 12 month period?Yes or No
  • Date it was givenDate
    Shown when “Has this information been given to all residents in the current 12 month period?” is Yes
  • How was it given?Choose one
    • Letter to each flat
    • Email
    • Noticeboard and letter
    • Handed to residents
    • Other (describe)
    Shown when “Has this information been given to all residents in the current 12 month period?” is Yes
  • CheckThe information must be given to all residents within each period of 12 months, and to a new resident as soon as reasonably practicable after they move in.
    Shown when “Has this information been given to all residents in the current 12 month period?” is No
  • How residents report a faultShort answer

Inspector sign-off

  • WarningYou recorded that at least one door failed. Check that the remedial work and its target date are filled in.
    Shown when “Did any door fail?” is Yes
  • Inspector name*Short answer
  • Position or companyShort answer
  • Inspector signatureSignature

See it filled in

A completed fire door inspection report, made by SiteSurvey from a fictional site visit: every answer, the photos, the guidance that applied and the sign-off, ready to send as a PDF.

See completed form (PDF) ↗

Fire door inspection FAQs

How often must fire doors be checked?

In England, regulation 10 of the Fire Safety (England) Regulations 2022 applies to multi-occupied residential buildings with a top storey more than 11 metres above ground. There, communal fire doors must be checked at least every 3 months, and the responsible person must use best endeavours to check flat entrance doors at least every 12 months. For other buildings the regulation sets no frequency, so follow the fire risk assessment.

What if a resident will not let me in to check their door?

Record the steps you took. For each flat entrance door the form asks whether access was given, and if not, whether you wrote, visited, phoned or offered a choice of times. The 12 month record then lists the flats where access was not granted and what will be tried next.

What is the maximum gap on a fire door?

GOV.UK guidance gives the industry standard that the gap between the door and the frame should never be more than 4 mm, except at the bottom. It gives no figure for the gap under the door, so the form asks for the limit from the door's own documents or the fire risk assessment and flags any gap over it.

What must residents be told about fire doors?

Regulation 10 requires residents to be told that fire doors should be kept shut when not in use, that self-closing devices should not be tampered with, and that faults or damage should be reported immediately. The form records whether this was given to all residents in the current 12 month period, when and how.

Does the checker need to be a specialist?

No. GOV.UK guidance says the checks should be simple and basic, and the form's door checks are visual and need no tools. Whether each door is the right type for its location is a matter for the fire risk assessment, and the form lets you refer anything to the assessor.

Can I record the checks offline?

In the SiteSurvey app, yes. The form works offline, takes photos of each door and defect, collects the inspector's signature and produces a PDF report or share link when it syncs.

Can AI check a fire door from a video?

It can help. This form's Walk Cam field carries an inspector brief with four points and 18 checks: the door and signage, the gaps, the seals and hinges, and the closer. Film each point in the SiteSurvey app and the AI inspector suggests pass, fail or cannot assess within about ten seconds, with each defect boxed on a still from the clip. It reads a gap only when a gauge is in shot and says cannot assess rather than guess. It is coming in the next SiteSurvey app update, in early access.

Does the AI inspector replace a competent fire door inspector?

No. It suggests and the inspector decides. Every point has Accept and Change, every finding has Dismiss, and nothing reaches the form or the report until the inspector confirms it. The report names the inspector and carries the line AI-assisted inspection, verdicts confirmed by the inspector. Whether a door is the right type for its location remains a matter for the fire risk assessment.