Form library · Fire safety

Communal and flat entrance fire door checks

Fire door checks for blocks of flats under regulation 10 of the Fire Safety (England) Regulations 2022. Record whether the building is over 11 metres and the type of check, then each door: scan its tag, communal or flat entrance, access gained and attempts made, the self-closer, latching, gaps and seals, and damage, with photos, a result and who will repair it by when. The form counts doors needing repair and flats with no access, and records when residents were last given the fire door information. Every question is listed below, and you can fill the live form in on this page.

Ready to use from the form library, and every question is yours to edit. Trial from £1, cancel any time.

Try it on your phone

Try it on this phone

Fill in the communal fire door checks on your phone now

See how the communal fire door checks looks on your phone

Scan the code with your phone camera. It opens the real form, no sign-up needed.

Open the live example and fill it in, just as your team would on site. No sign-up needed.

See it on this phone

Every question is editable. Add this form to your account, then change the wording, add or remove questions and options, and make it fit your own jobs.

Or start your trial with this form ready →

Prefer paper? Download a printable copy: PDF or Word

One email, and we won't add you to a mailing list.

How often must fire doors in flats be checked?

Under regulation 10 of the Fire Safety (England) Regulations 2022, in buildings over 11 metres high with two or more flats, the responsible person must check fire doors in communal areas at least every 3 months, and use best endeavours to check flat entrance fire doors at least every 12 months, including that self-closing devices work. Residents must also be given fire door information.

Last updated . Facts checked by the SiteSurvey team on 17 October 2026 against regulation 10 of the Fire Safety (England) Regulations 2022 (fire doors) and GOV.UK: fact sheet on fire doors (regulation 10).

Try the communal fire door checks form live

Answer a few questions and watch it adapt. Your answers are not saved, and any photos you add are deleted within the hour.

Live form: Residential Fire Door ChecksOpen full screen ↗
See a filled-in example

Open the completed example to see fictional readings, notes, photos and calculations. Choose Blank form to try entering your own answers.

Want to see one filled in? See a completed communal fire door checks report (PDF), made by SiteSurvey from a fictional site visit.

Every question in the communal fire door checks template

Fire door checks for blocks of flats under the Fire Safety (England) Regulations 2022: the building's top storey height, quarterly communal and annual flat entrance door checks, self-closers, gaps, seals and damage, counts of doors passed and needing repair, access attempts and resident information. 3 sections and 52 questions. Follow-up questions and guidance appear only when an answer calls for them, so the person on site never sees the ones that do not apply.

Make it your own: every question is editable

This is a starting point, not a fixed form. Once it is in your SiteSurvey account you can reword any question, add or remove questions, sections and answer options, and add your own logo, so it fits the way your team works and the jobs you do.

Details you only enter once

Add this form to a project in SiteSurvey and it fills in what the project already knows, so nobody on site retypes it and every form on the job uses the same names. Anything filled in can still be changed.

  • Project: the project name
  • Client: the project's customer
  • Site: the site, when the form is opened for a space or a product
  • Site address: the site address, from the space or the project

Building and check

  • ProjectShort answer
    Fills in from the project name
  • ClientShort answer
    Fills in from the project's customer
  • Site*Short answer
    Fills in from the site, when the form is opened for a space or a product
  • Site addressShort answer
    Fills in from the site address, from the space or the project
  • Building locationShort answer

    Mark it at the main entrance. On an estate it shows which block was checked. Tap Mark current location on site. It saves the coordinates, a grid reference and the accuracy.

  • Date*Date
  • TimeTime
  • Checked by*Short answer
  • Is the building above 11 metres in height (measured to the top storey)?Yes or No
  • Height of the top storey floor above ground (m)Number

    Measured from the ground on the lowest side to the floor of the top storey (Approved Document B, Appendix D). Take it from the drawings or a survey, or measure it from a photo of the elevation with a door as the reference. Measuring from a photo gives an estimate.

    Shown when “Is the building above 11 metres in height (measured to the top storey)?” is answered
  • Height against 11 mWorked out by the form
    Shown only when the answers above make it relevant
  • CheckThe measured height and the answer above do not agree. Confirm the height from the drawings or a survey before deciding whether the regulation 10 checks apply.
    Shown only when the answers above make it relevant
  • Check*Choose one
    • Quarterly communal fire doors
    • Annual flat entrance doors
    • Both
  • Date of the last communal fire door checkDate
    Shown only when the answers above make it relevant
  • Days since the last communal checkWorked out by the form
    Shown only when the answers above make it relevant
  • CheckMore than 92 days since the last communal check. Above 11 m, regulation 10 requires communal fire doors to be checked at least every 3 months.
    Shown only when the answers above make it relevant
  • GuidanceRegulation 10, Fire Safety (England) Regulations 2022: in a building with two or more flats that is above 11 m, check any fire doors in communal areas at least every 3 months, and use best endeavours to check flat entrance fire doors at least every 12 months. The checks must include that the self-closing devices work. Keep a record of the flat door checks, including the steps taken to try to gain access where it was not granted.
  • GuidanceNot above 11 m: the 3-monthly and 12-monthly checks in regulation 10 do not apply, but where residents would evacuate through common parts they must still be given the fire door information, and fire doors must still be maintained under the Fire Safety Order.
    Shown when “Is the building above 11 metres in height (measured to the top storey)?” is No

Doors

  • Floors and levels
    Repeat for each entry. Each one asks:
    • Floor or level*Short answer
    • Doors on this floor
      Repeat for each door. Each one asks:
      • Door reference or flat number*Short answer
      • Scan the door tagScan a label: door id, certification number

        Optional. Scan the label or tag to capture its numbers.

      • DoorChoose one
        • Communal
        • Flat entrance
      • Access gained?Yes or No
        Shown when “Door” is “Flat entrance”
      • Attempts to gain access (dates and how)Short answer
        Shown when “Access gained?” is No
      • Self-closer closes the door fully into the frameChoose one
        • OK
        • Defect
      • Latches and is not wedged or held openChoose one
        • OK
        • Defect
      • Gaps and seals (intumescent and smoke seals)Choose one
        • OK
        • Defect
      • Door leaf, frame, glazing and hinges undamagedChoose one
        • OK
        • Defect
      • What is wrong?Short answer
        Shown only when the answers above make it relevant
      • PhotosPhotos
      • Result*Choose one
        • Pass
        • Repair needed
        • No access
      • Repair: who will do it, and by whenShort answer
        Shown when “Result” is “Repair needed”
    • This floor: doors checkedWorked out by the form
    • This floor: communalWorked out by the form
    • This floor: flat entranceWorked out by the form
    • This floor: passedWorked out by the form
    • This floor: doors needing repairWorked out by the form
    • This floor: flat doors with no accessWorked out by the form
    • This floor: self-closers with a defectWorked out by the form
    • This floor: gaps or seals with a defectWorked out by the form
  • Doors checkedWorked out by the form
  • CommunalWorked out by the form
  • Flat entranceWorked out by the form
  • PassedWorked out by the form
  • Doors needing repairWorked out by the form
  • Flat doors with no accessWorked out by the form
  • Self-closers with a defectWorked out by the form
  • Gaps or seals with a defectWorked out by the form
  • Next communal fire door check dueDate

    Regulation 10: at least every 3 months for buildings above 11 m.

    Shown only when the answers above make it relevant
  • Days to the next communal checkWorked out by the form
    Shown when “Date” is answered and “Next communal fire door check due” is answered
  • Next flat entrance door check dueDate

    Regulation 10: best endeavours at least every 12 months for buildings above 11 m.

    Shown only when the answers above make it relevant
  • Days to the next flat door checkWorked out by the form
    Shown when “Date” is answered and “Next flat entrance door check due” is answered
  • CheckA next check date is before the date of this check. Check the dates.
    Shown only when the answers above make it relevant
  • CheckThe next communal check is more than 92 days away. Above 11 m, communal fire doors must be checked at least every 3 months.
    Shown only when the answers above make it relevant
  • CheckAt least one self-closer is not working. Regulation 10 checks must include that the self-closing devices work. Record who will repair it and by when.
    Shown only when the answers above make it relevant

Resident information and sign-off

  • Have residents had the fire door information in the last 12 months?Yes or No
  • Date it was last given to all residentsDate
    Shown when “Have residents had the fire door information in the last 12 months?” is Yes
  • WarningResidents must be told that fire doors should be kept shut when not in use, that residents and their guests should not tamper with the self-closing devices, and that faults or damage to doors should be reported to the responsible person straight away. New residents are told as soon as reasonably practicable after moving in, and all residents within each 12 months.
    Shown when “Have residents had the fire door information in the last 12 months?” is No
  • Completed by*Short answer
  • SignatureSignature

See it filled in

A completed communal fire door checks report, made by SiteSurvey from a fictional site visit: every answer, the photos, the guidance that applied and the sign-off, ready to send as a PDF.

See completed form (PDF) ↗

Communal fire door checks FAQs

What if I cannot get into a flat?

The duty for flat entrance doors is best endeavours, and regulation 10 requires a record of the steps taken to try to gain access. Record each attempt, with dates and how; GOV.UK's fact sheet suggests keeping the correspondence with residents as evidence. The form counts the flats with no access.

What must residents be told?

That fire doors should be kept shut when not in use, that residents and their guests should not tamper with self-closing devices, and that faults or damage should be reported to the responsible person straight away. New residents must be told as soon as reasonably practicable after moving in, and all residents within each 12 months.

What does each check cover?

The self-closer closing the door fully, latching, gaps and intumescent and smoke seals, and damage to the leaf, frame, glazing and hinges.

What about buildings under 11 metres?

The 3-monthly and 12-monthly checks in regulation 10 apply above 11 metres. The resident information applies to all buildings with two or more flats whose residents would evacuate through common parts, and fire doors must still be maintained under the Fire Safety Order.

How is this different from a fire door inspection?

These are the routine checks for obvious damage or faults that regulation 10 requires. GOV.UK's fact sheet says it should not be necessary to engage a specialist for them, and that a detailed technical check of a door's fire resistance is a matter for the fire risk assessment.

Who uses this?

Building managers, housing associations, managing agents, RMCs and fire door contractors.