Form library · Facilities and maintenance
Schedule of test results template
An electrical test sheet for a distribution board. Record the supply, Ze or Zdb and prospective fault current, then each circuit with its protective device, cable sizes, continuity and ring readings, insulation resistance, polarity, measured and maximum Zs, RCD time and the RCD or AFDD test button. The form warns on insulation resistance under 1 MΩ at 500 V, Zs over the maximum and an RCD slower than 300 ms. Every question is listed below, and you can fill the live form in on this page.
Ready to use from the form library, and every question is yours to edit. Trial from £1, cancel any time.
Try it on your phone
Try it on this phone
Fill in the schedule of test results on your phone now
See how the schedule of test results looks on your phone
Scan the code with your phone camera. It opens the real form, no sign-up needed.
Open the live example and fill it in, just as your team would on site. No sign-up needed.
See it on this phoneEvery question is editable. Add this form to your account, then change the wording, add or remove questions and options, and make it fit your own jobs.
What goes on a schedule of test results?
A schedule of test results records, for each circuit on a board, the circuit number and description, the protective device type and rating, the live and protective conductor sizes, continuity (R1 + R2, and r1, rn and r2 for a ring), insulation resistance live to live and live to earth with the test voltage, polarity, the maximum measured earth fault loop impedance Zs, the RCD disconnection time and the test button checks. The IET model schedule for BS 7671:2018+A4:2026 has these columns.
Last updated . Facts checked by the SiteSurvey team on 17 October 2026 against IET: BS 7671:2018+A4:2026 model forms, condition report and schedule of test results, IET: BS 7671 inspection and testing FAQs (insulation resistance test voltage), IET Wiring Matters: the 1 megohm minimum insulation resistance, IET Wiring Matters, July 2022: RCD operating times and GOV.UK: electrical safety standards in the private and social rented sectors.
Try the schedule of test results form live
Answer a few questions and watch it adapt. Your answers are not saved, and any photos you add are deleted within the hour.
Open the completed example to see fictional readings, notes, photos and calculations. Choose Blank form to try entering your own answers.
Want to see one filled in? See a completed schedule of test results report (PDF), made by SiteSurvey from a fictional site visit.
Every question in the schedule of test results template
An electrical test results schedule for a distribution board: every circuit with its device, cables, continuity, insulation resistance, polarity, Zs and RCD times, with warnings on readings that fail. 3 sections and 70 questions. Follow-up questions and guidance appear only when an answer calls for them, so the person on site never sees the ones that do not apply.
Make it your own: every question is editable
This is a starting point, not a fixed form. Once it is in your SiteSurvey account you can reword any question, add or remove questions, sections and answer options, and add your own logo, so it fits the way your team works and the jobs you do.
Details you only enter once
Add this form to a project in SiteSurvey and it fills in what the project already knows, so nobody on site retypes it and every form on the job uses the same names. Anything filled in can still be changed.
- Project: the project name
- Client: the project's customer
- Site: the site, when the form is opened for a space or a product
- Site address: the site address, from the space or the project
Board and supply
- ProjectShort answerFills in from the project name
- ClientShort answerFills in from the project's customer
- Site*Short answerFills in from the site, when the form is opened for a space or a product
- Site addressShort answerFills in from the site address, from the space or the project
- Date of the tests*Date
- TimeTime
- Tested by*Short answer
- Distribution board reference and location*Short answer
- Scan the board labelScan a label: asset number
Optional. Scan the label or tag to capture its numbers.
- Photos of the boardPhotos
Optional. The board with its cover on and off, the circuit chart and anything you found.
- Earthing arrangementChoose one
- TN-C-S (PME)
- TN-S
- TT
- Other
- Earth fault loop impedance at the board, Ze or Zdb (Ω)Number
Ze at the origin, or Zdb at a sub-distribution board.
- Prospective fault current (kA)Number
- Test instrument, serial number and calibration dateShort answer
- CheckThis is a site record of the readings and checks. It is not the BS 7671 certificate or schedule itself: issue that from your registration scheme's or your certification software.
Circuits
- Circuits testedRepeat for each circuit. Each one asks:
- Circuit number*Short answer
- Circuit description*Short answer
- Points servedNumber
- Live conductor (mm²)Number
- Protective conductor (mm²)Number
- Protective deviceChoose one
- MCB type B
- MCB type C
- MCB type D
- RCBO type B
- RCBO type C
- BS 88 fuse
- BS 1361 fuse
- BS 3036 rewireable fuse
- Other
- Rating (A)Number
- RCD typeChoose one
- Type AC
- Type A
- Type F
- Type B
- No RCD
- Ring final circuit?Yes or No
- Ring end to end r1 (Ω)NumberShown when “Ring final circuit?” is Yes
- Ring end to end rn (Ω)NumberShown when “Ring final circuit?” is Yes
- Ring end to end r2 (Ω)NumberShown when “Ring final circuit?” is Yes
- Difference between r1 and rn (Ω)Worked out by the formShown when “Ring final circuit?” is Yes and “Ring end to end r1 (Ω)” is answered and “Ring end to end rn (Ω)” is answered
- (r1 + r2) / 4, the expected R1 + R2 for the ring (Ω)Worked out by the formShown when “Ring final circuit?” is Yes and “Ring end to end r1 (Ω)” is answered and “Ring end to end r2 (Ω)” is answered
- Continuity R1 + R2 (Ω)Number
- Ze + (R1 + R2) (Ω)Worked out by the form
Ze or Zdb from page 1 plus R1 + R2. Compare it with the measured Zs below.
Shown when “Earth fault loop impedance at the board, Ze or Zdb (Ω)” is answered and “Continuity R1 + R2 (Ω)” is answered - Insulation resistance test voltageChoose one
- 250 V
- 500 V
- 1000 V
- Insulation resistance, live to live (MΩ)Number
- Insulation resistance, live to earth (MΩ)Number
- WarningBelow 1 MΩ. The IET gives 1 MΩ as the minimum insulation resistance, with a 500 V d.c. test for circuits up to 500 V. Investigate before the circuit is put into service.Shown only when the answers above make it relevant
- PolarityChoose one
- Correct
- Fault
- Earth fault loop impedance Zs, measured (Ω)Number
- Maximum permitted Zs for this device (Ω)Number
From the BS 7671 tables or the device manufacturer.
- Measured Zs as a share of the maximum (%)Worked out by the formShown only when the answers above make it relevant
- WarningMeasured Zs is above the maximum permitted for this protective device. The device may not disconnect in time.Shown only when the answers above make it relevant
- RCD operating time at rated residual current (ms)Number
- WarningOver 300 ms at the rated residual current. IET guidance gives 300 ms as the maximum for a general non-delay RCD (an S type time-delayed RCD may take up to 500 ms). Check or replace the RCD.Shown only when the answers above make it relevant
- RCD or AFDD test button operatesChoose one
- Yes
- No
- Not fitted
- Result*Choose one
- Pass
- Fail
- CheckRecorded as a pass, but a reading above is outside a limit the form checks. Check the reading and the result.Shown only when the answers above make it relevant
- ObservationsNotesShown only when the answers above make it relevant
- c_f_passWorked out by the form
- c_f_failWorked out by the form
- c_f_irWorked out by the form
- c_f_zsWorked out by the form
- c_f_rcdWorked out by the form
- Circuit retest readingsRepeat for each reading. Each one asks:
- Reading date and time*Short answer
- Continuity R1 + R2 (Ω)Number
- Insulation test voltage (V)Choose one
- 250
- 500
- 1000
- Insulation resistance: live to earth (MΩ)Number
- Earth fault loop impedance Zs (Ω)Number
- RCD operating time (ms)Number
- Recorded resultChoose one
- Not assessed
- Pass
- Fail
- Not tested
- Notes / action takenNotes
- Photos for this readingPhotos
- Circuits testedWorked out by the form
- Circuits passedWorked out by the form
- Circuits failedWorked out by the form
- Insulation under 1 MΩ at 500 VWorked out by the form
- Zs over the maximumWorked out by the form
- RCD slower than 300 msWorked out by the form
- Highest Zs as a share of its maximum (%)Worked out by the formShown only when the answers above make it relevant
Actions and sign-off
- Are further actions needed?Yes or No
- CheckA circuit failed, but no further action is recorded. Add what needs doing, who will do it and when.Shown only when the answers above make it relevant
- Further actionsRepeat for each action. Each one asks:Shown when “Are further actions needed?” is Yes
- What needs doing?*Notes
- Who will do it?Short answer
- Due dateDate
- StatusChoose one
- Open
- In progress
- Completed
- Inspector name*Short answer
- Position or companyShort answer
- Inspector signatureSignature
- CheckSigning records what was found on the day. It does not make unsafe equipment safe or replace a thorough examination, design check or service by a competent person.
See it filled in
A completed schedule of test results report, made by SiteSurvey from a fictional site visit: every answer, the photos, the guidance that applied and the sign-off, ready to send as a PDF.
Schedule of test results FAQs
What is the minimum insulation resistance?
The IET gives 1 MΩ as the minimum insulation resistance, with a 500 V d.c. test for circuits up to and including 500 V (other than SELV and PELV). The form shows a warning when either reading at 500 V is under 1 MΩ, so the circuit is investigated before it is put into service.
How does it check Zs?
Enter the measured earth fault loop impedance and the maximum permitted for that protective device, from the BS 7671 tables or the device manufacturer. The IET schedule asks you to note the source when the maximum is not from the BS 7671 tables. The form warns when the measured value is higher, because the device may not disconnect in time.
What about RCD tests?
Record the operating time from an alternating current test at the rated residual current. IET guidance gives 300 ms as the maximum for a general non-delay RCD, and 130 to 500 ms for an S type time-delayed RCD. The form warns over 300 ms, and records whether the RCD or AFDD test button works.
Is this the BS 7671 schedule itself?
No. It is a site record of the readings, so they are captured on the phone with the board and circuit details. Issue the formal certificate and schedule from your registration scheme's or your certification software.
Can I record ring final circuits?
Yes. Answer that the circuit is a ring and the form asks for the end-to-end r1, rn and r2 readings as well as R1 + R2.
Who uses this?
Electricians testing new work, periodic inspections and remedial work, and facilities teams keeping results for each board. In England, private and social landlords must have the electrical installation inspected and tested at least every 5 years, and the report includes a schedule of test results.
Related
Related templates
Templates that go with the schedule of test results form
Planned maintenance visit: records seen, asset by asset tasks, water temperatures, work done and next visit.
Build or update an asset register: each asset with its tag, make, model, serial, position (GPS outside), condition, life and photos, totals by condition and life, and changes to the register.
Inspection round for plant: asset condition, refrigerant and leak checks, pressure vessels, next due dates.
Job sheet for a reactive or planned job: safety before starting, work done, parts used, tests, outcome and customer sign-off.