Form library · Fire safety
Emergency lighting test log
An emergency lighting log book for the monthly function test and the annual full duration test. Add each luminaire or circuit, scan its label, record the charge indicator and a pass or fail, and photograph any fault. On the annual test the form checks the test ran for the full rated duration and asks about cover while the batteries recharge, and any failure asks whether the responsible person was told. Every question is listed below, and you can fill the live form in on this page.
Ready to use from the form library, and every question is yours to edit. Trial from £1, cancel any time.
Try it on your phone
Try it on this phone
Fill in the emergency lighting test on your phone now
See how the emergency lighting test looks on your phone
Scan the code with your phone camera. It opens the real form, no sign-up needed.
Open the live example and fill it in, just as your team would on site. No sign-up needed.
See it on this phoneEvery question is editable. Add this form to your account, then change the wording, add or remove questions and options, and make it fit your own jobs.
How often should emergency lighting be tested?
Home Office guidance says testing would typically include a daily visual check of any central controls, a monthly function test, operating the test facility for long enough to make sure each emergency lamp lights, and an annual full discharge test. Batteries typically take 24 hours to recharge after a full discharge, and the premises should not be re-occupied until the emergency lighting is fully working unless other arrangements have been made. It is good practice to keep a record of tests.
Last updated . Facts checked by the SiteSurvey team on 17 October 2026 against the Home Office guide Fire safety risk assessment: offices and shops, article 14 of the Regulatory Reform (Fire Safety) Order 2005 and article 17 of the Regulatory Reform (Fire Safety) Order 2005.
Try the emergency lighting test form live
Answer a few questions and watch it adapt. Your answers are not saved, and any photos you add are deleted within the hour.
Open the completed example to see fictional readings, notes, photos and calculations. Choose Blank form to try entering your own answers.
Want to see one filled in? See a completed emergency lighting test report (PDF), made by SiteSurvey from a fictional site visit.
Every question in the emergency lighting test template
An emergency lighting test record: monthly function tests and the annual full duration test for each luminaire or circuit, with charge indicators, faults, photos and a warning when a test ends early. 3 sections and 60 questions. Follow-up questions and guidance appear only when an answer calls for them, so the person on site never sees the ones that do not apply.
Make it your own: every question is editable
This is a starting point, not a fixed form. Once it is in your SiteSurvey account you can reword any question, add or remove questions, sections and answer options, and add your own logo, so it fits the way your team works and the jobs you do.
Details you only enter once
Add this form to a project in SiteSurvey and it fills in what the project already knows, so nobody on site retypes it and every form on the job uses the same names. Anything filled in can still be changed.
- Project: the project name
- Client: the project's customer
- Site: the site, when the form is opened for a space or a product
- Site address: the site address, from the space or the project
Test details
- ProjectShort answerFills in from the project name
- ClientShort answerFills in from the project's customer
- Site*Short answerFills in from the site, when the form is opened for a space or a product
- Site addressShort answerFills in from the site address, from the space or the project
- Date of the test*Date
- TimeTime
- Tested by, name and role*Short answer
- Responsible person for the premisesShort answer
- Which test?*Choose one
- Monthly function test
- Annual full duration test
- Type of systemChoose one
- Self-contained luminaires
- Central battery system
- Both
- Date of the last monthly function testDate
Before today's test. From the log book or the last record.
- Date of the last annual full duration testDate
Before today's test, if today is an annual test.
- Days since the last monthly testWorked out by the formShown when “Date of the last monthly function test” is answered and “Date of the test” is answered
- Days since the last full duration testWorked out by the formShown when “Date of the last annual full duration test” is answered and “Date of the test” is answered
- Routine tests overdueWorked out by the form
The monthly test counts as overdue after 31 days, the annual test after 366 days.
Shown only when the answers above make it relevant - CheckMore than a month since the last monthly function test. Record why it was missed and get the monthly tests back on track.Shown only when the answers above make it relevant
- CheckMore than a year since the last full duration test. Book the annual full discharge test the Home Office guide describes.Shown only when the answers above make it relevant
- GuidanceHome Office guide Fire safety risk assessment: offices and shops. Testing would typically include a daily visual check of any central controls, a monthly function test, operating the test facility for long enough to make sure each emergency lamp lights, and an annual full discharge test. It is good practice to keep a record of tests.
- CheckSources. BS 5266-1 (Emergency lighting, code of practice) and BS EN 50172 (Emergency escape lighting systems) set a monthly function test of every luminaire and an annual test for the full rated duration, with results kept in a log book. The Regulatory Reform (Fire Safety) Order 2005, article 17, requires the responsible person to keep emergency lighting maintained in efficient working order and good repair, by a competent person.
- Rated duration of the system (hours)Number
From the design or commissioning documents for the system.
Shown when “Which test?” is “Annual full duration test” - How long did the test run? (minutes)NumberShown when “Which test?” is “Annual full duration test”
- Rated duration covered (%)Worked out by the formShown only when the answers above make it relevant
- Minutes short of the rated durationWorked out by the formShown only when the answers above make it relevant
- WarningTest not complete. The test did not run for the full rated duration. Record it as incomplete and arrange a repeat.Shown only when the answers above make it relevant
- CheckAfter a full discharge test, batteries typically take 24 hours to recharge. The Home Office guide says the premises should not be re-occupied until the emergency lighting is fully working again, unless other arrangements have been made.Shown when “Which test?” is “Annual full duration test”
- Are other arrangements in place until the batteries have recharged?Yes or NoShown when “Which test?” is “Annual full duration test”
Luminaires tested
- Record the results forChoose one
- Each luminaire
- Each circuit
- Luminaires by floor or areaRepeat for each entry. Each one asks:
- Floor or area*Short answer
For example Ground floor, First floor east wing or Plant room
- Luminaires or circuits in this areaRepeat for each entry. Each one asks:
- Luminaire or circuit reference*Short answer
- Scan the luminaire labelScan a label: asset number, serial number
Optional. Scan the label or tag to capture its numbers.
- Position in this area*Short answer
- TypeChoose one
- Non-maintained bulkhead
- Maintained bulkhead
- Exit sign
- Downlight
- Twin spot
- Central battery fitting
- Other
- Charge indicatorChoose one
- Lit
- Not lit
- No indicator fitted
- Result*Choose one
- Pass
- Fail
- What was wrong?Choose one
- Did not light
- Went out before the end of the test
- Dim
- Charge indicator not lit
- Damaged or missing diffuser
- Missing
Shown only when the answers above make it relevant - Went out after (minutes)Number
From the start of the test. Shows how far short of the rated duration this fitting fell.
Shown when “What was wrong?” is “Went out before the end of the test” - WarningFailed. Record the fault in the log book and tell the responsible person before you leave. The area this covers may not be lit if the normal lighting fails.Shown only when the answers above make it relevant
- Photos of the faultPhotosShown only when the answers above make it relevant
- Action taken or neededNotesShown only when the answers above make it relevant
- This floor or area: luminaires or circuits testedWorked out by the form
- This floor or area: passedWorked out by the form
- This floor or area: failedWorked out by the form
- This floor or area: charge indicator not litWorked out by the form
- This floor or area: went out before the endWorked out by the form
- Luminaires or circuits testedWorked out by the form
- PassedWorked out by the form
- FailedWorked out by the form
- Passed (%)Worked out by the formShown only when the answers above make it relevant
- Charge indicator not litWorked out by the form
- Went out before the endWorked out by the form
- WarningFailures found. Each failed fitting may leave its area unlit if the normal lighting fails: tell the responsible person before you leave and set an action for each.Shown only when the answers above make it relevant
- Has the responsible person been told about the failures?Yes or NoShown only when the answers above make it relevant
- Did the test cover every luminaire in the building?Yes or No
- Which were missed, and when will they be done?NotesShown when “Did the test cover every luminaire in the building?” is No
- Has this test been entered in the emergency lighting log book?Yes or No
Actions and sign-off
- Are further actions needed?Yes or No
- Further actionsRepeat for each action. Each one asks:Shown when “Are further actions needed?” is Yes
- What needs doing?*Notes
- PriorityChoose one
- Urgent
- High
- Medium
- Low
- Who will do it?Short answer
- Due dateDate
- StatusChoose one
- Open
- In progress
- Completed
- Next monthly function test dueDate
BS 5266-1: every month.
- Days until the monthly testWorked out by the formShown when “Date of the test” is answered and “Next monthly function test due” is answered
- Next annual full duration test dueDate
BS 5266-1: every 12 months.
- Days until the annual testWorked out by the formShown when “Date of the test” is answered and “Next annual full duration test due” is answered
- CheckCheck the dates. A next test date is before the date of this test.Shown only when the answers above make it relevant
- Inspector name*Short answer
- Position or companyShort answer
- Inspector signatureSignature
- CheckSigning records what was found on the day. It does not make unsafe equipment safe or replace a thorough examination, design check or service by a competent person.
See it filled in
A completed emergency lighting test report, made by SiteSurvey from a fictional site visit: every answer, the photos, the guidance that applied and the sign-off, ready to send as a PDF.
Emergency lighting test FAQs
What is the difference between the monthly and annual test?
The monthly function test is short: operate the test switch for long enough to see each emergency lamp light. The annual test runs the system on its batteries for its full rated duration. Choose the test at the start of the form; the annual test asks for the rated duration and how long the test ran, and warns you if it ended early.
How do I know the rated duration?
From the design or commissioning documents for the system. Do not assume it: a 3 hour system tested for 1 hour has not had a full duration test. The form compares the minutes the test ran with the rated hours you enter, and warns when the test ended early.
What happens after the annual test?
Batteries typically take 24 hours to recharge after a full discharge. The Home Office guide says the premises should not be re-occupied until the emergency lighting is working again, unless other arrangements are in place. The form asks whether those arrangements are in place.
Can I record results by circuit instead of by luminaire?
Yes. Choose each luminaire or each circuit at the start of the luminaires section. Each entry has its own reference, location, type, charge indicator, pass or fail, and for a failure the fault, photos and the action taken. The form counts passes and failures.
Is testing emergency lighting a legal requirement?
In England and Wales, article 14 of the Regulatory Reform (Fire Safety) Order 2005 requires emergency routes and exits that need lighting to have emergency lighting if the normal lighting fails, and article 17 requires the responsible person to keep that equipment subject to a suitable system of maintenance and in efficient working order. Regular tests with a written record are a practical way to show this.
How is this different from the fire safety checklist?
The fire safety checklist covers a whole routine visit: extinguishers, emergency lighting, the weekly alarm test, escape routes and drills. This log goes deeper on emergency lighting alone, with a label scan for each luminaire and the full duration test checks.
Related
Related templates
Templates that go with the emergency lighting test form
Door by door checks (gaps, seals, closers, signage, glazing), 12 month flat entrance door record and remedial work list.
Routine fire safety checks: extinguishers, emergency lighting tests, the weekly alarm test, escape routes, signs and fire drills, with actions.
Fire risk assessment following the five steps in GOV.UK guidance: hazards, people at risk, fire precautions, emergency plan and training, findings with actions and review.
A PEEP for one person who would need help to leave a building in a fire: how they are warned, their route, refuges, equipment, helpers, practice and review.
Use this emergency lighting test form with your team
Add it from the form library in one click, change any question, and every completed form becomes a branded PDF report.
Start your trial →