Electrical installation certificate template
A site record for new electrical work that needs an Electrical Installation Certificate (EIC). Record the type and extent of the work, the supply, earthing and bonding, then each circuit with its protective device, cables, R1 + R2, insulation resistance, polarity, Zs and RCD time. The form flags failing readings, counts the circuits that pass and fail, and records the inspection, comments on the existing installation, any departures and who signed for design, construction and testing. Every question is listed below, and you can fill the live form in on this page.
Ready to use from the form library, and every question is yours to edit. Trial from £1, cancel any time.
Try it on your phone
Try it on this phone
Fill in the electrical installation certificate on your phone now
See how the electrical installation certificate looks on your phone
Scan the code with your phone camera. It opens the real form, no sign-up needed.
Open the live example and fill it in, just as your team would on site. No sign-up needed.
See it on this phoneEvery question is editable. Add this form to your account, then change the wording, add or remove questions and options, and make it fit your own jobs.
When do you need an electrical installation certificate?
The notes on the IET model form say an Electrical Installation Certificate (EIC) is used for a new installation, for an addition or alteration that introduces one or more new circuits, and for replacing a consumer unit or distribution board. It records who was responsible for design, construction and inspection and testing, and is only valid with its schedule of inspections and schedules of circuit details and test results. An addition or alteration with no new circuit may go on a minor works certificate instead.
Last updated . Facts checked by the SiteSurvey team on 17 October 2026 against IET model Electrical Installation Certificate and its notes (BS 7671:2018+A4:2026), Approved Document P (2013 edition): notifiable electrical work in dwellings and IET: BS 7671 model forms (EIC, minor works, EICR).
Try the electrical installation certificate form live
Answer a few questions and watch it adapt. Your answers are not saved, and any photos you add are deleted within the hour.
Open the completed example to see fictional readings, notes, photos and calculations. Choose Blank form to try entering your own answers.
Want to see one filled in? See a completed electrical installation certificate report (PDF), made by SiteSurvey from a fictional site visit.
Every question in the electrical installation certificate template
A site record for new electrical work that needs an Electrical Installation Certificate: scope, supply and earthing, bonding, each new circuit with its tests, inspection items, departures and the three sign-offs. 5 sections and 65 questions. Follow-up questions and guidance appear only when an answer calls for them, so the person on site never sees the ones that do not apply.
Make it your own: every question is editable
This is a starting point, not a fixed form. Once it is in your SiteSurvey account you can reword any question, add or remove questions, sections and answer options, and add your own logo, so it fits the way your team works and the jobs you do.
Details you only enter once
Add this form to a project in SiteSurvey and it fills in what the project already knows, so nobody on site retypes it and every form on the job uses the same names. Anything filled in can still be changed.
- Project: the project name
- Client: the project's customer
- Site: the site, when the form is opened for a space or a product
- Site address: the site address, from the space or the project
Work
- ProjectShort answerFills in from the project name
- ClientShort answerFills in from the project's customer
- Site*Short answerFills in from the site, when the form is opened for a space or a product
- Site addressShort answerFills in from the site address, from the space or the project
- Date completed*Date
- TimeTime
- Contractor and registration scheme number*Short answer
- Type of work*Choose one
- New installation
- Rewire
- Addition with one or more new circuits
- Consumer unit replacement
- Alteration
- Extent of the work covered*Notes
- GuidanceThe notes on the IET model Electrical Installation Certificate say it is used for a new installation, for an addition or alteration that introduces one or more new circuits, and for replacing a consumer unit or distribution board. An addition or alteration that does not introduce a new circuit may go on a Minor Electrical Installation Works Certificate.
- Is the work in a dwelling in England?Yes or No
- CheckApproved Document P: in a dwelling, installing a new circuit, replacing a consumer unit, or any addition or alteration to existing circuits in a special location (such as the space around a bath or shower) is notifiable. It must be certified by a registered competent person, a registered third-party certifier or a building control body.Shown when “Is the work in a dwelling in England?” is Yes
- CheckThis is a site record of the work and test results, not the certificate itself. The formal certificate and its schedules are issued from the registration scheme's or certification software.
Supply and earthing
- Earthing arrangement*Choose one
- TN-C-S (PME)
- TN-S
- TT
- SupplyChoose one
- Single-phase
- Three-phase
- External earth fault loop impedance Ze (Ω)Number
- Prospective fault current (kA)Number
- Main switch rating (A)Number
- Main earthing conductor size (mm²)Number
- Earth electrode resistance (Ω)NumberShown when “Earthing arrangement” is “TT”
- CheckAbove 200 Ω. IET guidance notes that an earth electrode resistance above 200 Ω may not be stable, for example as the ground dries out or freezes. Check the electrode and the reading.Shown only when the answers above make it relevant
- Earth electrode positionShort answer
Mark current location standing at the electrode or its inspection pit, so the next person testing can find it.
Shown when “Earthing arrangement” is “TT” - Main protective bonding connected toTick all that apply
- Water
- Gas
- Oil
- Structural steel
- Lightning protection
- Other (describe)
- None present
- Distribution board or consumer unitShort answer
- Scan the board labelScan a label: serial number, model number
Optional. Scan the label or tag to capture its numbers.
- Photos of the board and labellingPhotos
Circuits and tests
- CircuitsRepeat for each circuit. Each one asks:
- Circuit number*Short answer
- DescriptionShort answer
- Protective deviceChoose one
- MCB type B
- MCB type C
- MCB type D
- RCBO type B
- RCBO type C
- BS 88 fuse
- BS 1361 fuse
- BS 3036 rewireable fuse
- Other
- Rating (A)Number
- RCD typeChoose one
- Type AC
- Type A
- Type F
- Type B
- No RCD
- Live conductor (mm²)Number
- Protective conductor (mm²)Number
- Continuity R1 + R2 (Ω)Number
- Insulation resistance test voltageChoose one
- 250 V
- 500 V
- 1000 V
- Insulation resistance, live to live (MΩ)Number
- Insulation resistance, live to earth (MΩ)Number
- Minimum for this test voltage (MΩ)Worked out by the form
BS 7671 Table 64: 0.5 MΩ for SELV and PELV circuits tested at 250 V, and 1 MΩ for circuits tested at 500 V (up to 500 V) or 1000 V (above 500 V).
Shown when “Insulation resistance test voltage” is answered - Insulation resistance against the minimumWorked out by the formShown only when the answers above make it relevant
- WarningBelow the minimum insulation resistance in BS 7671 Table 64 (1 MΩ at a 500 V or 1000 V test, 0.5 MΩ for SELV and PELV at 250 V). Investigate before the circuit is put into service.Shown when “Insulation resistance against the minimum” is “Below the minimum”
- PolarityChoose one
- Correct
- Fault
- Earth fault loop impedance Zs, measured (Ω)Number
- Maximum permitted Zs for this device (Ω)Number
From the BS 7671 tables or the device manufacturer. The form compares the measured value with what you enter here.
- Measured Zs as a share of the maximum (%)Worked out by the formShown only when the answers above make it relevant
- Zs against the maximumWorked out by the formShown only when the answers above make it relevant
- WarningMeasured Zs is above the maximum permitted for this protective device. The device may not disconnect in time.Shown only when the answers above make it relevant
- RCD operating time at rated residual current (ms)Number
- RCD time against 300 msWorked out by the formShown only when the answers above make it relevant
- WarningOver 300 ms at the rated residual current. IET guidance gives 300 ms as the maximum for a general non-delay RCD (an S type time-delayed RCD may take up to 500 ms). Check or replace the RCD.Shown only when the answers above make it relevant
- Result*Choose one
- Pass
- Fail
- What failed and what was doneNotesShown only when the answers above make it relevant
- Circuits recordedWorked out by the form
- Circuits failedWorked out by the form
- Circuits passedWorked out by the form
- Insulation resistance below the minimumWorked out by the form
- Zs above the maximum enteredWorked out by the form
- RCD over 300 msWorked out by the form
- Polarity faultsWorked out by the form
- CheckOne or more readings above are outside a limit. Each one needs a note of what was found and done, and a retest, before the circuit is put into service.Shown only when the answers above make it relevant
- GuidanceThe checks compare readings with limits you can look up: insulation resistance with BS 7671 Table 64, Zs with the maximum you enter for each device, and RCD times with 300 ms. They help spot a reading that needs a second look. They do not replace the inspector's judgement or the certificate.
Inspection and departures
- Inspected and correct*Tick all that apply
- Cables selected and installed correctly
- Protective devices suit the circuits
- Isolation and switching
- Fire barriers and sealing
- Labels and warning notices
- Surge protection considered
- Additional protection by RCD where required
- Comments on the existing installationNotes
Defects seen in the existing installation that this work does not cover.
Shown only when the answers above make it relevant - Are there any departures from BS 7671?Yes or No
- Departures and why they are acceptableNotesShown when “Are there any departures from BS 7671?” is Yes
- Recommended date of next inspectionDate
Sign-off
- Did one person do the design, construction and inspection and testing?Yes or No
- Design: name*Short answer
If one person did the design, construction and inspection and testing, they sign here for all three.
- Design: signatureSignature
- Construction: nameShort answerShown when “Did one person do the design, construction and inspection and testing?” is No
- Construction: signatureSignatureShown when “Did one person do the design, construction and inspection and testing?” is No
- Inspection and testing: nameShort answerShown when “Did one person do the design, construction and inspection and testing?” is No
- Inspection and testing: signatureSignatureShown when “Did one person do the design, construction and inspection and testing?” is No
- Client nameShort answer
- Client signatureSignature
See it filled in
A completed electrical installation certificate report, made by SiteSurvey from a fictional site visit: every answer, the photos, the guidance that applied and the sign-off, ready to send as a PDF.
Electrical installation certificate FAQs
Who signs an EIC?
The IET model form has signatures for the design, the construction and the inspection and testing, and a person responsible for more than one signs in each place. A single-signature version is used where one person did all three. The form asks which applies and shows the right signature boxes.
Is this the certificate itself?
No. It is a site record of the work and the readings, with photos of the board. Issue the formal certificate and its schedules from your registration scheme's or your certification software.
Does the work need notifying?
In a dwelling in England, Approved Document P makes a new circuit, a consumer unit replacement, or an addition or alteration to circuits in a special location (such as around a bath or shower) notifiable. It must be certified by a registered competent person, a registered third-party certifier or building control. The form shows this when you say the work is in a dwelling.
What readings are recorded?
The supply: earthing arrangement, Ze, prospective fault current and main switch. Then for each circuit: device and rating, RCD type, conductor sizes, R1 + R2, insulation resistance with the test voltage, polarity, measured and maximum Zs and RCD operating time, with a pass or fail.
What does it warn about?
It flags an insulation resistance reading below 1 MΩ at a 500 V test, a measured Zs above the maximum you enter for the device, and an RCD time over 300 ms. A failed circuit asks what failed and what was done.
Who uses this?
Electricians and electrical contractors on rewires, consumer unit changes, extensions and new installations.
Related
Related templates
Templates that go with the electrical installation certificate form
An electrical minor works site record: the work done, the circuit it was on, earthing and protection, continuity, insulation resistance, polarity, Zs and RCD tests, departures and Part P notification.
An electrical test results schedule for a distribution board: every circuit with its device, cables, continuity, insulation resistance, polarity, Zs and RCD times, with warnings on readings that fail.
Site record for a periodic inspection: installation details, extent and limitations, supply and earthing, boards, schedule of circuits and test results, coded observations with photos, and the overall assessment.
Use this electrical installation certificate form with your team
Add it from the form library in one click, change any question, and every completed form becomes a branded PDF report.
Start your trial →