Pressure system inspection record
An examination record for a pressure system under the Pressure Systems Safety Regulations 2000. Record the system and its written scheme of examination, then each item: scan its data plate, record the safe operating limit, the protective devices tested, its condition, repairs needed and the date to complete them, and the date after which it must not be operated. The form warns on unsafe items, counts repairs, records whether the scheme is still suitable and the date of the report, and ends with the signatures. Every question is listed below, and you can fill the live form in on this page.
Ready to use from the form library, and every question is yours to edit. Trial from £1, cancel any time.
Try it on your phone
Try it on this phone
Fill in the pressure system inspection on your phone now
See how the pressure system inspection looks on your phone
Scan the code with your phone camera. It opens the real form, no sign-up needed.
Open the live example and fill it in, just as your team would on site. No sign-up needed.
See it on this phoneEvery question is editable. Add this form to your account, then change the wording, add or remove questions and options, and make it fit your own jobs.
What is a written scheme of examination?
Under the Pressure Systems Safety Regulations 2000, a written scheme of examination identifies the items in a pressure system, the parts to examine, the nature of each examination including tests of protective devices, the preparation needed, the maximum interval between examinations, and the competent person who certified it. A competent person then examines the system in line with the scheme and reports.
Last updated . Facts checked by the SiteSurvey team on 17 October 2026 against regulation 8 of the Pressure Systems Safety Regulations 2000 (written scheme of examination), regulation 9 of the Pressure Systems Safety Regulations 2000, regulation 10 of PSSR 2000 (action in case of imminent danger) and HSE INDG178: written schemes of examination.
Try the pressure system inspection form live
Answer a few questions and watch it adapt. Your answers are not saved, and any photos you add are deleted within the hour.
Open the completed example to see fictional readings, notes, photos and calculations. Choose Blank form to try entering your own answers.
Want to see one filled in? See a completed pressure system inspection report (PDF), made by SiteSurvey from a fictional site visit.
Every question in the pressure system inspection template
A pressure system examination record under PSSR: the written scheme, each item with its safe operating limit, protective devices, condition, repairs and dates, the next examination and the competent person's report. 3 sections and 53 questions. Follow-up questions and guidance appear only when an answer calls for them, so the person on site never sees the ones that do not apply.
Make it your own: every question is editable
This is a starting point, not a fixed form. Once it is in your SiteSurvey account you can reword any question, add or remove questions, sections and answer options, and add your own logo, so it fits the way your team works and the jobs you do.
Details you only enter once
Add this form to a project in SiteSurvey and it fills in what the project already knows, so nobody on site retypes it and every form on the job uses the same names. Anything filled in can still be changed.
- Project: the project name
- Client: the project's customer
- Site: the site, when the form is opened for a space or a product
- Site address: the site address, from the space or the project
System and scheme
- ProjectShort answerFills in from the project name
- ClientShort answerFills in from the project's customer
- Site*Short answerFills in from the site, when the form is opened for a space or a product
- Site addressShort answerFills in from the site address, from the space or the project
- Examination date*Date
- TimeTime
- Competent person*Short answer
- CompanyShort answer
- System (for example compressed air system, steam boiler)*Short answer
- Written scheme of examination referenceShort answer
- Written scheme certified onDate
- GuidanceHSE INDG178: a written scheme of examination identifies the items in the system, the parts to examine, the nature of each examination, including tests of protective devices, the preparation needed, the maximum interval between examinations, and the competent person who certified it.
Items examined
- Items by plant room or areaRepeat for each entry. Each one asks:
- Plant room or area*Short answer
For example Compressor house or Boiler room
- Items examined hereRepeat for each item. Each one asks:
- Item*Short answer
- Scan the data plateScan a label: serial number, asset number
Optional. Scan the label or tag to capture its numbers.
- TypeChoose one
- Air receiver
- Steam boiler
- Autoclave or steriliser
- Pressure vessel
- Pipework
- Safety valve
- Other
- Safe operating limit (bar)Number
- Normal operating pressure (bar)Number
As found on the gauge in normal running, or from the user's records.
- Operating pressure against the limitWorked out by the formShown when “Normal operating pressure (bar)” is answered and “Safe operating limit (bar)” is answered
- WarningThe normal operating pressure is above the safe operating limit. Record the repairs, modifications or changes to the safe operating limit below.Shown only when the answers above make it relevant
- it_op_flagWorked out by the form
- Protective devices testedTick all that apply
- Safety valve
- Pressure gauge
- Pressure switch
- Low water alarm
- Drain valve
- Safety valve set pressure (bar)NumberShown when “Protective devices tested” includes “Safety valve”
- Set pressure in the written scheme (bar)NumberShown when “Protective devices tested” includes “Safety valve”
- Safety valve against the schemeWorked out by the formShown when “Safety valve set pressure (bar)” is answered and “Set pressure in the written scheme (bar)” is answered
- it_sv_flagWorked out by the form
- Condition*Choose one
- Satisfactory
- Repairs needed
- Unsafe: do not use
- Repairs, modifications or changes to safe operating limitsNotesShown only when the answers above make it relevant
- Complete repairs byDateShown when “Condition” is “Repairs needed”
- WarningImminent danger (PSSR regulation 10). The competent person must give the user a written report straight away, specifying the repairs, modifications or changes needed, and send the same particulars to the enforcing authority within 14 days. The system, or that part of it, must not be operated until they are done.Shown when “Condition” is “Unsafe: do not use”
- Do not operate after (next examination due)Date
- Days to the next examinationWorked out by the formShown when “Examination date” is answered and “Do not operate after (next examination due)” is answered
- it_due60_flagWorked out by the form
- PhotosPhotos
- This plant room or area: items examinedWorked out by the form
- This plant room or area: items satisfactoryWorked out by the form
- This plant room or area: items unsafeWorked out by the form
- This plant room or area: items needing repairsWorked out by the form
- This plant room or area: operating above the limitWorked out by the form
- This plant room or area: safety valves differing from the schemeWorked out by the form
- This plant room or area: next examination due within 60 daysWorked out by the form
- Items examinedWorked out by the form
- Items satisfactoryWorked out by the form
- Items unsafeWorked out by the form
- Items needing repairsWorked out by the form
- Operating above the limitWorked out by the form
- Safety valves differing from the schemeWorked out by the form
- Next examination due within 60 daysWorked out by the form
- CheckAn item is running above its safe operating limit, or a safety valve is set differently from the written scheme. Record the action needed in the item and in the report.Shown only when the answers above make it relevant
Report
- Is the written scheme still suitable?Choose one
- Suitable
- Should be modified
- Changes needed to the schemeNotesShown when “Is the written scheme still suitable?” is “Should be modified”
- CheckPSSR regulation 9: the competent person sends a signed, dated written report to the user (or the owner of a mobile system) as soon as practicable, to arrive within 28 days of the examination, or before the date set in the report for repairs, if that is sooner.
- Date of the reportDate
- Days from examination to reportWorked out by the formShown only when the answers above make it relevant
- CheckMore than 28 days after the examination. PSSR regulation 9 asks for the report to reach the user within 28 days of the examination, or sooner if repairs are due first.Shown only when the answers above make it relevant
- Examiner name*Short answer
- Examiner signatureSignature
- Received for the user or owner byShort answer
- SignatureSignature
See it filled in
A completed pressure system inspection report, made by SiteSurvey from a fictional site visit: every answer, the photos, the guidance that applied and the sign-off, ready to send as a PDF.
Pressure system inspection FAQs
When is the report due?
PSSR regulation 9 requires the competent person to send a signed, dated written report to the user (or the owner of a mobile system) as soon as practicable, to arrive within 28 days of the examination, or before the date the report sets for repairs if that is sooner.
What must the report say?
The parts examined, their condition and the results; any repairs, modifications or changes to safe operating limits with a date to complete them; the date after which the system must not be operated without another examination; and whether the scheme is suitable or should be modified.
Which systems are covered?
HSE INDG178 says relevant fluids include compressed or liquefied gas, including air, above 0.5 bar, pressurised hot water above 110°C, and steam at any pressure. Air receivers, steam boilers and autoclaves are common examples.
What if an item is unsafe?
Under PSSR regulation 10, where the competent person thinks there will be imminent danger unless repairs or changes are made, they must give the user a written report straight away and send the same details to the enforcing authority within 14 days. The system, or that part of it, must not be operated until the work is done. The form warns and counts unsafe items.
Does it replace the written scheme?
No. Under PSSR regulation 8, the user or owner must make sure the scheme has been drawn up, or certified as suitable, by a competent person. This form records each examination against it.
Who uses this?
Engineer surveyors, insurers' inspection teams, compressor and boiler service companies, and maintenance managers.
Related
Related templates
Templates that go with the pressure system inspection form
A compressed-air maintenance record with compressor and receiver details, isolation, visible checks, operating readings, service work and handback.
A gas boiler service record with appliance identity, engineer scope, manufacturer checks, measured results, defects, remedial work and customer handover.
A LOLER thorough examination record: each item of lifting equipment with its identity, SWL, the basis of the examination, defects, whether they are dangerous, the next examination date and the examiner's declaration.
Use this pressure system inspection form with your team
Add it from the form library in one click, change any question, and every completed form becomes a branded PDF report.
Start your trial →